HXGN15-12L HV Switchgear Metal-clad AC Ring Main Unit

HXGN15-12L is a metal-clad AC ring main unit designed for medium-voltage power distribution systems. It integrates load break switches, circuit breakers, busbar, cable, and control compartments within a compact and fully enclosed structure. The unit supports SF6 or vacuum switching technology and provides reliable performance for urban and rural distribution networks. With a robust aluminium-zinc plated steel enclosure and well-separated functional compartments, HXGN15-12L ensures safe operation, flexible configuration, and long-term stability in medium-voltage distribution applications.

Share to:

Overview

XGN15-12L HV switchgear metal enclosed AC ring main unit is a new HV apparatus which introduced from abroad and is accord with the requirement of rural distribution and city distribution in nation. Main switch, operation mechanism and component use the SFL-12 model SF6 switch equipment produced by ABB company or FLN36-12D model SF6 switch equipment produced by our company. Also can use the HAD/US model SF6 circuit breaker or VD4-S model vacuum circuit breaker produced by company ABB according to requirement of customer operation type is manual and motor.

Product Feature

Panel structure:
The panel body is enclosed by 2 mm aluminium-zinc plated steel plate after multi-bending. It is simple, firm, delicate and peculiar.

1. Busbar compartment
The busbar compartment is located in the top and connect with neighboring panel.

2. Load break switch
Load break switch is a separated unit with SF6 gas.

3. Cable compartment
Approximate 75% room for connecting cable and installing fuse, earthing switch and PT.

4. Mechanism chamber and interlock
The chamber consists of operating mechanism, mechanism interlock, position indicator, auxiliary contact trip coil, power indicator and interlock.

5. LV chamber
LV compartment is located in the top. It mainly user for installing instrument, relay and motor.

6. Circuit breaker compartment
The circuit breaker (SF6 or Vacuum) is located below load break switch.

Operating Conditions

  1. Ambient temperature: -25 ~ +40;
  2. Altitude: 1000m;
  3. Relative humidity: daily average 95%, monthly average 90%;
  4. Occasions without flammable and explosive matter, without corrosive chemical and frequent severe vibration, without strong shake.

Model

Technical Specification

ItemUnitParameter
Rated voltagekV10
Highest working voltagekV12
Rated frequencyHz50/60
Main busbar rated currentA630
Main loop, earthing loop rated short time withstand currentkA/s20/3
Main loop, earthing loop rated peak withstand currentkA50
Main loop, earthing loop rated short circuit making currentkA50
Load break switch full capacity breaking timeTimes100
Fuse breaking currentkA31.5–50
Mechanical lifeTimes2000
Rated transfer currentA1700
1min P.F. withstand (virtual value), phase to phase, earth/across open contactskV42/48
Lightning impulse withstand voltage (peak) phase to phase, earth/across open contactskV75/85
Secondary loop 1min P.F. withstandkV2
Protection degreeIP3X

Outline And Dimension

ItemUnitParameter
Width of circuit breaker panelmm750
Other width of panelmm375 / 500
Heightmm1600 / 1850
Depthmm980
Height of LV casemm450

CONTACT FOR MORE INFORMATION

Scroll to Top

Request A Quote