KYN28-24 Withdrawable Metal-clad Switchgear

KYN28-24 is a withdrawable metal-clad air-insulated switchgear designed for medium-voltage power distribution systems up to 24 kV. It is used for receiving, distributing, and controlling electrical energy in industrial and public power networks. The switchgear adopts a vacuum circuit breaker with a reliable withdrawable structure, supporting flexible installation and convenient maintenance. With comprehensive mechanical interlocking, stable insulation performance, and compliance with IEC and relevant national standards, KYN28-24 ensures safe, reliable, and long-term operation for indoor medium-voltage applications.

Share to:

Overview

KYN28A-24 Series switchgear panel is a MV air-insulated switchgear (AIS) for primary distribution, with vacuum circuit-breaker has been designed for the various operating requirements in public and industrial medium-voltage distribution systems.

This panel applies to 13.8~24kV 3 phase AC 50Hz / 60Hz network for receiving and distributing power energy and also for control, monitor and protection.

It can be arranged for single bus, single-bus sectionalizing system.

It accords to IEC62271-200 <<AC Metal Enclosed Switchgear and Control Equipment above 1kV and below 52kV>>,
IEC694<<Standard Common Clause for HV Switchgear and Control Equipment>>,
GB3906<<3~35kV AC Metal Enclosed Switchgear>>,
DL404<<Order Specification for Indoor AC HV Switchgear>>,
DIN.VDE0670<<AC Switchgear at Rated Voltage over 1kV>> and so on.

It has perfect and reliable prevention function against false-operation.

Operating Conditions

Normal operating conditions, according to the IEC International Standards listed below, for indoor switchgear.

Ambient air temperature
• Less than or equal to 40°C
• Less than or equal to 35°C on average over 24 hours
• Greater than or equal to -5°C (-25°C on request)

Altitude
• Less than or equal to 1000 m;
• Above 1000 m, a derating coefficient is applied (please consult us)

Atmosphere
• No dust, smoke, or corrosive, or inflammable gas and vapor, or salt
• Earthquake intensity Magnitude 8

Humidity
• Average relative humidity over a 24 hour period ≤ 95%
• Average relative humidity over a 1 month period ≤ 90%
• Average vapor pressure over a 24 hour period ≤ 2.2 kPa
• Average vapor pressure over a 1 month period ≤ 1.8 kPa

Storage conditions

In order to retain all of the functional unit’s qualities when stored for prolonged periods, we recommend that the equipment is stored in its original packaging, in dry conditions, and sheltered from the sun and rain at a temperature ranging from -25°C up to +55°C.

Model

Technical Characteristics

ItemUnitData
Rated voltagekV13.8, 15, 17.5, 20, 22, 24
Rated insulation level
1 min. P.F. withstand voltage (phases to ground / gaps)kV50 / 60
Lightning impulse withstand voltage (phases to ground / gaps)kV125 / 145
Rated frequencyHz50 / 60
Rated currentA630, 1250, 1600, 2000, 2500, 3150
Rated short-time withstand current (4s)kA16, 20, 25, 31.5, 40, 50
Rated peak withstand current※kA40, 50, 63, 80, 100, 125
Protection classEnclosure: IP4X, IP2X (VCB Door opened)
Outline dimension (width × depth × height)mm1000(800) × 1800 × 2400
Weightkg840–1500