KYN28A-12 Withdrawable Metal-clad Switchgear

KYN28A-12 is a withdrawable metal-clad air-insulated switchgear designed for medium-voltage power distribution systems up to 12 kV. It is used for receiving, distributing, and controlling electrical energy in industrial and public power networks. The switchgear adopts a vacuum circuit breaker with a compact withdrawable structure, allowing flexible configuration and convenient maintenance. With reliable mechanical interlocking, stable insulation performance, and compliance with IEC and relevant standards, KYN28A-12 ensures safe, efficient, and long-term operation for indoor medium-voltage applications.

Share to:

Overview

KYN28A-12 Series switchgear panel is a MV air-insulated switchgear (AIS) for primary distribution, with vacuum circuit-breaker has been designed for the various operating requirements in public and industrial medium-voltage distribution systems. This panel applies to 3.6~12kV 3 phase AC 50Hz / 60Hz network for receiving and distributing power energy and also for control, monitor and protection. It can be arranged for single bus, single-bus sectionalizing system. It accords to IEC62271-200 <>, IEC694<>, GB3906<<3~35kV AC Metal Enclosed Switchgear>>, DL404<>, DIN.VDE0670<> and so on. It has perfect and reliable prevention function against false-operation.

Operating Conditions

Normal operating conditions, according to the IEC International Standards listed below, for indoor switchgear.

Ambient air temperature
• Less than or equal to 40°C
• Less than or equal to 35°C on average over 24 hours
• Greater than or equal to -5°C (-25°C on request)

Altitude
• Less than or equal to 1000 m;
• Above 1000 m, a derating coefficient is applied (please consult us)

Atmosphere
• No dust, smoke, or corrosive, or inflammable gas and vapor, or salt
• Earthquake intensity: Magnitude 8

Humidity
• Average relative humidity over a 24 hour period ≤ 95%
• Average relative humidity over a 1 month period ≤ 90%
• Average vapor pressure over a 24 hour period ≤ 2.2 kPa
• Average vapor pressure over a 1 month period ≤ 1.8 kPa

Model

Technical Characteristics

ItemUnitData
Rated voltagekV3.6, 7.2, 12
Rated insulation level
1 min. P.F. withstand voltage (phases to ground / gaps)kV42 / 48
Lightning impulse withstand voltage (phases to ground / gaps)kV75 / 85
Rated frequencyHz50 / 60
Rated currentA630, 1250, 1600, 2000, 2500, 3150, 4000, 5000
Rated short-time withstand current (4s)kA16, 20, 25, 31.5, 40, 50
Rated peak withstand current※kA40, 50, 63, 80, 100, 125
Protection classEnclosure: IP4X, IP2X (VCB Door opened)
Outline dimension (width × depth × height)mm800 (550, 650, 1000) × 1500 (1300, 1670, 2000) × 2200
Weightkg800–1200

Construction

CONTACT FOR MORE INFORMATION

Scroll to Top