Overview
KYN61-40.5 Series switchgear panel is a MV air-insulated switchgear (AIS) for primary distribution, with vacuum circuit-breaker has been designed for the various operating requirements in public and industrial medium-voltage distribution systems. This panel applies to 27~40.5kV 3 phase AC 50Hz / 60Hz network for receiving and distributing power energy and also for control, monitor and protection. It can be arranged for single bus, single-bus sectionalizing system. It accords to IEC62271-200 <>, IEC694<>, GB3906<<3~35kV AC Metal Enclosed Switchgear>>, DL404<>, DIN.VDE0670<> and so on. It has perfect and reliable prevention function against false-operation.
Operating Conditions
Normal operating conditions, according to the IEC International Standards listed below, for indoor switchgear.
Ambient air temperature
• Less than or equal to 40°C
• Less than or equal to 35°C on average over 24 hours
• Greater than or equal to -5°C (-25°C on request)
Altitude
• Less than or equal to 1000 m;
• Above 1000 m, a derating coefficient is applied (please consult us)
Atmosphere
• No dust, smoke, or corrosive, or inflammable gas and vapor, or salt
• Earthquake intensity: Magnitude 8
Humidity
• Average relative humidity over a 24 hour period ≤ 95%
• Average relative humidity over a 1 month period ≤ 90%
• Average vapor pressure over a 24 hour period ≤ 2.2 kPa
• Average vapor pressure over a 1 month period ≤ 1.8 kPa
Model

Feature
• Provides Middle Rolling and Floor Roiling two different withdrawable types, can meet all our customers’ technical requirements and operating features.
• Reliable “anti-5” mechanical latch, convenient and safe maintenance,
• Both VCB of ZN85-40.5 / VS1-40.5 developed by our company and VD4, VB2 AND 3AH manufactured by other companies around the world can be matched with the switchgear.
Technical characteristics
| Item | Unit | Data |
|---|---|---|
| Rated voltage | KV | 27,33, 36,38,40.5 |
| Rated insulation level | ||
| 1 min. P.F. withstand voltage (phases to ground/gaps) | KV | 85/95 |
| Lightning impulse withstand voltage (phases to ground/gaps) | KV | 185/215 |
| Rated frequency | Hz | 50/60 |
| Rated current | A | 630,1250,1600,2000,2500,3150 |
| Rated short-time withstand current (4s) | KA | 16,20,25,31.5,40,50 |
| Rated peak withstand current※ | KA | 40,50,63,80,100,125 |
| Protection class | Enclosure: IP4X, IP2X (VCB Door opened) | |
| Outline dimension (width×depth×height) | mm | 1400(1200)×2800(2600)×260(2400) |
| weight | kg | 1300–1600 |